Copper Conductors Single core 700C thermoplastic insulated cables (e.g. PVC Singles), non-armoured with or without sheath. All values assume an ambient temperature of 300C and a conductor operating temperature of 700C.
Conductor CSA | Reference Method A (enclosed in conduit in thermally insulating wall etc) | Reference Method B (enclosed in conduit on a wall or in trunking etc) | Reference Method C (clipped direct) | Reference method F (in free air or on a perforated cable tray horizontal or vertical) | |||||||
Touching | Spaced by one diameter | ||||||||||
2 cables, 1ph ac or dc flat 3 cables, 3ph ac flat | |||||||||||
2 cables, 1ph ac or dc | 3 or 4 cables, 3ph ac | 2 cables, 1ph ac or dc | 3 or 4 cables, 3ph ac | 2 cables, 1ph ac or dc | 3 or 4 cables, 3ph ac | 2 cables, 1ph ac or dc flat | 3 cables
3ph ac flat
|
3 cables, 3ph ac trefoil | Horizontal | Vertical | |
1mm2 | 11 | 10.5 | 13.5 | 12 | 15.5 | 14 | |||||
1.5mm2 | 14.5 | 13.5 | 17.5 | 15.5 | 20 | 18 | |||||
2.5mm2 | 20 | 18 | 24 | 21 | 27 | 25 | |||||
4mm2 | 26 | 24 | 32 | 28 | 37 | 33 | |||||
6mm2 | 34 | 31 | 41 | 36 | 47 | 43 | |||||
10mm2 | 46 | 42 | 57 | 50 | 65 | 59 | |||||
16mm2 | 61 | 56 | 76 | 68 | 87 | 79 | |||||
25mm2 | 80 | 73 | 101 | 89 | 114 | 104 | 131 | 114 | 110 | 146 | 130 |
35mm2 | 99 | 89 | 125 | 110 | 141 | 129 | 162 | 143 | 137 | 181 | 162 |
Table 4D2A – Multicore 700c thermoplastic insulated & thermoplastic sheathed cables (e.g. PVC T&E), nonarmoured. All values assume an ambient temperature of 300c and a conductor operating temperature of 700c.
Conductor CSA | Reference Method A (enclosed in conduit in thermally insulating wall etc) | Reference Method B (enclosed in conduit on a wall or in trunking etc) | Reference Method C (clipped direct) | Reference Method E (in free air or on a perforated cable tray, horizontal or vertical) | ||||
1 two core cable*, 1ph ac or dc | 1 three core cable* or 1 four core cable, 3ph ac | 1 two core cable*, 1ph ac or dc | 1 three core cable* or 1 four core cable, 3ph ac | 1 two core cable*, 1ph ac or dc | 1 three core cable* or 1 four core cable, 3ph ac | 1 two core cable*, 1ph ac or dc | 1 three core cable* or 1 four core cable, 3ph ac | |
1mm2 | 11 | 10 | 13 | 11.5 | 15 | 13.5 | 17 | 14.5 |
1.5mm2 | 14 | 13 | 16.5 | 15 | 19.5 | 17.5 | 22 | 18.5 |
2.5mm2 | 18.5 | 17.5 | 23 | 20 | 27 | 24 | 30 | 25 |
4mm2 | 25 | 23 | 30 | 27 | 36 | 32 | 40 | 34 |
6mm2 | 32 | 29 | 38 | 34 | 46 | 41 | 51 | 43 |
10mm2 | 43 | 39 | 52 | 46 | 63 | 57 | 70 | 60 |
16mm2 | 57 | 52 | 69 | 62 | 85 | 76 | 94 | 80 |
*with or without a protective conductor
Multicore 700c armoured thermoplastic insulated cables (e.g. SWA cable). All values assume that air ambient temperature of 300c, ground ambient temperature of 200c & conductor operating temperature of 700c.
Conductor CSA | Reference Method C (clipped direct) | Reference Method E (in free air or on a perforated cable tray, horizontal or vertical) | Reference Method D (direct in ground or in ducting in ground, in or around buildings) | |||
1 two core cable, 1ph ac or dc | 1 three core cable or 1 four core cable, 3ph ac | 1 two core cable, 1ph ac or dc | 1 three core cable or 1 four core cable, 3ph ac | 1 two core cable, 1ph ac or dc | 1 three core cable or 1 four core cable, 3ph ac | |
1.5mm2 | 21 | 18 | 22 | 19 | 22 | 18 |
2.5mm2 | 28 | 25 | 31 | 26 | 29 | 24 |
4mm2 | 38 | 33 | 41 | 35 | 37 | 30 |
6mm2 | 49 | 42 | 53 | 45 | 46 | 38 |
10mm2 | 67 | 58 | 72 | 62 | 60 | 50 |
16mm2 | 89 | 77 | 97 | 83 | 78 | 64 |
25mm2 | 118 | 102 | 128 | 110 | 99 | 82 |
35mm2 | 145 | 125 | 157 | 135 | 119 | 98 |
50mm2 | 175 | 151 | 190 | 163 | 140 | 116 |
70mm2 | 222 | 192 | 241 | 207 | 173 | 143 |
95mm2 | 269 | 231 | 291 | 251 | 204 | 169 |
Flexible cords, non-armoured
Conductor CSA (mm2) | Current carrying capacity | Max. supported weight (Kg) See Regs 522.7.2 & 559.6.1.5 | |
1ph ac | 3ph ac | ||
0.5mm2 | 3 | 3 | 2 |
0.75mm2 | 6 | 6 | 3 |
1mm2 | 10 | 10 | 5 |
1.25mm2 | 13 | - | 5 |
1.5mm2 | 16 | 16 | 5 |
2.5mm2 | 25 | 20 | 5 |
4mm2 | 32 | 25 | 5 |